Строительный блокнот  Introduction to electronics 

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 [ 199 ] 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300

(rms turreiu) = \J !l + % \fj-

me (16.19)

= (rms voltage)

By use ofEq. (1Й.Й), the average power is

Vl f (16.20)

: (mis voltage)

Insertion of Eqs. (16.19) and (16.20) into Eq. (16.15) then shows that the power factor is unity. Thus, if the load is linear and purely resistive, then the power factor is unity rcg;irdlcss ofthe harmonic content of v(f). The harmonic content of the load current waveform i{t) is identical to that of v(/), and all harmonics result in the transfer of energy to the load. This raises the possibility that one could construct a power distribution system based on nonsinusoidal waveforms in which the energy is efficiently transferred to the load.

16.3.2 Nonlineui- Dynumical Load, Sinusoidal Voltage

If the voltage vit) contains a fundamental component but no dc component or harmonics, so that - Vj = 13 = ... = 0, then harmonics in /(r) do not restdt in transmission of net energy to the load. The average power expression, Eq. (16.fi), becomes

Л = -с>(ф,-0) C-iJ

However, the harmonics in /(f) do affect the value of the rms current:

Hence, as in example 1 (Fig. 16.2), harmonics cause the load to draw more rras ctirrent from the source, but not more average power Increasing the current harmonics does not cause more energy to be transferred to the load, but does cause additional losses in series resistive elements Rseries

Also, the presence ofload dynamics and reactive elements, which causes the phase of the fundamental components of the voltage and current todiffer (8, - ф,), also reduces the power factor. The :os (Ф, - й) tetm in the average power Eq. (16.21) becomes less than unity. However, the tins value of the current, Eq. (16.22), dt)es not depend on the phase. So shifting the phase of /(;) with respect to vit) reduces the average power without changing the rras voltage or current, and hence the power factor is reduced.

By substituting Eqs. (16.21) and (16.22) into (16.15). we can express the power factor for the sinusoidal voltage in the following form:



(power factor) =

cos (ф,-0,))

(16.23)

= (distortion factor) (disptaeetneitt factor)

So when the voitage contains no harmonics, then the power factor can be written as the prt)diict of two terms. The first, called the distortionfactor, is the ratio t)f the rms fundamental component of the current to the total runs value of the current

(distortion factor) -

(tuts fundamental current) (rms curreti:)

(16,24)

The second term of Eq. (16.23) is called the displacement factor, and is the cosine of the angle between the fundamental components of the voltage and current waveforms.

The Total Harnwnic Distortion (THD) is defined as the ratio of the rms value of the waveform not including the fundamental, to the rms fundamental magnitude. When no dc is present, this can be written:

(THD) =

(16.25)

The total hartnonic distortitm and the distortion factor are closely related. Comparison of Eqs. (16.24) and (16.25), with /ц = 0, eads to

(distoition factor)

= -

V I + (THD)

(16.26)

This equation is plotted iit Fig. lfi.5. The distortion factor of a waveform with a moderate amount of distortion is quite close to unity. For example, if the waveform contains third harmonic whose magnitude is

100%

Fig. 16.5 Distortion factor vs. total harmonic distortion.





Fig, 16,6 Cotiventioiial peaJt detMtion rectifier,

100% 1

Sfl% -

60% -

40% -

20% -

0% -

100%

THD = 136% Distortion factor = 59%

15% 15

I 3 5 7 9 11 13 15 17 19 Harmonic ntmber

rig. 16,7 Typical ВС line current spectrum nf a peak detection rectifier. Harmonics 1 to 19 are shown,

10% of the fimdaraental, the distortion factor is 99.5%. Increasing the third harmonic to 20% decreases the distortion factor to 98%, and a 33% harmonic magnittide yields a distortion factor of 95%. So the power factor is not significantly degraded by the presence of harmonics unless the harmonics are quite large in magnitude.

An example of a case in which the distortion factor is much less than unity is the conventional peak detection rectifier of Fig. 16.6. In this circuit, the ac line current consists of short-duration current pulses occurring at the peak of the voltage waveform. The fundamental component ofthe line current is essentially in phase with the voltage, and the displacement factor is close ft) unity. However, the low-order current harmonics are quite large, close in magnitude to that ofthe fundamental-a typical current spectrum is given in Fig. 16.7. The distortion factor of peak detection rectifiers is usually in the range 55% to 65%. The resulting power factor is similar in value.

In North America, the standard 120 V power outlet is protected by ti 15 A circuit brealter. In consequence, the available load power quite limited. Derating the circuit breaker current by 20%, assuming typical efficiencies for the dc~dc converter and peak detection rectifier, and with a power factor of 55%, one obtains the following estimate for the maximum available dc load power:

(ac voltage) (derated breaker current) (power factor) (rectifier efficiency) = (120V) (iiO%ofl5A) (0,55) (0,98)

= 776W

(16.27)

The less-than-unity efficiency of a dc-dc converter would further reduce the available dc load power. U.sing a peak detectitm rectifier to supply a load power greater than this requires that the user install higher amperage anil/or higher voltage service, which is inconvenient and costly. The use of a rectifier



1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 [ 199 ] 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300